Operating InstructionsVEGABAR 634 … 20 mA/HARTDocument ID:32462Process pressure/Hydrostaticp
Two-wire electronics 4 … 20 mA/HART for power supply andmeasured value transmission over the same cable.The supply voltage range can differ depending o
The delivery must be checked for completeness and possible transitdamage immediately at receipt. Ascertained transit damage orconcealed defects must b
4 Mounting4.1 General instructionsMake sure that all parts of the instrument in contact with the measuredproduct, especially the sensor element, proce
Ventilation for the measuring cell is realised by means of a filterelement in the socket of the electronics housing. Ventilation for theelectronics hou
12Fig. 4: Temperatureranges1 Process temperature2 Ambient temperatureDanger:Instruments in the version "Oil and grease free for oxygen" shou
à Screw VEGABAR 63 into the welded socket. Tighten the hexagonon the process fitting with a suitable wrench. Wrench size, seechapter "Dimensions&q
Warning:The four screws of the socket housing must only be hand-screwed. Atorque > 5 Nm (3.688 lbf ft) can damage the wall mounting plate.16 VEGABA
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
Caution:Nogrease should be used when screwing the NPT cable gland orsteel tube into the threaded insert. Standard grease can containadditives that cor
11 Tightenthe compression nut of the cable entry. The seal ring mustcompletely encircle the cable12 Screw the housing cover onThe electrical connectio
Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .
2 Remove the housing socket from the mounting plate321Fig. 7: Componentsof the external housing for plics®devices1 Screws2 Wall mounting plate3 Cable
5.3 Wiring plan, single chamber housingThe following illustrations apply to the non-Ex as well as to the Ex-iaversion.1 243Fig. 8: Materialversions, s
I²CDisplay1 2 5 6 7 83412Fig. 9: Electronicsand connection compartment, single chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Spring
123465Fig. 11: Doublechamber housing1 Housing cover, connection compartment2 Blind stopper or plug M12 x 1 for VEGADIS 61 (optional)3 Housing cover, e
312Display1 2I²CFig. 13: Connectioncompartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection
5.5 Wiring plan double chamber housing Ex d1 2 345Fig. 15: Doublechamber housing1 Housing cover, connection compartment2 Blind stopper or plug M12 x 1
121 2Fig. 17: Connectioncompartment double chamber housing Ex d1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for connec
+-12Fig. 19: Wireassignment, connection cable1 brown (+) and blue (-) to power supply or to the processing system2 Shielding5.7 Wiring plan, external
5 6 7 81 2DisplayI²C45123Fig. 21: Electronicsand connection compartment1 Plug connector for VEGACONNECT (I²C interface)2 Spring-loaded terminals for c
1 2 3 4 6 3 4 1 2 5Fig. 22: Connectionof the sensor in the housing socket1 Brown2 Blue3 Yellow4 White5 Shielding6 Breather capillariesI2CDisplay11
7 Setup with PACTware and other adjustment programs7.1 Connect the PC via VEGACONNECT . . . . . . . . . . . .477.2 Parameter adjustment with PACTware
5.8 Switchon phaseAfter connecting VEGABAR 63 to power supply or after a voltagerecurrence, the instrument carries out a self-check for approx. 30seco
6 Setup with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,
Fig. 24: Mountingthe indicating and adjustment moduleNote:Ifyou intend to retrofit the instrument with an indicating and adjustmentmodule for continuou
6.3 Adjustment system1.1231Fig. 25: Indicatingand adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov
6.4 SetupprocedureIn HART-Multidrop mode (several sensors on one input) the addressmust be set before continuing with the parameter adjustment. You wi
Toselect the adjustment unit (in the example switching over from barto mbar) you have to proceed as follows:3)1 Push the [OK] button in the measured v
Unit of measurementDensity0001000kg/dm³6 Enter the requested density value with [->] and [+], confirm with[OK] and move to position correction with
5 Confirmwith [+] and move to max. adjustment with [->].The min. adjustment is finished.Information:For an adjustment with filling, you simply enter t
The position correction compensates the influence of the mountingposition or static pressure on the measurement. It does not influencethe adjustment val
▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displaye
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
Proceed as follows:1 Edit the mbar value in the menu item "zero" with [OK].Zero adjustment000.0 %P=+0000.0 mbar0000.0 mbar2 Set the requeste
A linearization is necessary for all vessels in which the vessel volumedoes not increase linearly with the level - e. g. with a cylindrical orspherica
Copy sensor dataCopy sensor data?Basic adjustmentIf the "Reset" (sensor-specific basic adjustment) is carried out, thesensor resets the value
FactorysettingLike basic adjustment, furthermore special parameters are reset todefault values.7)PointerThe min. and max. temperature or pressure valu
6.5 MenuschematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment1▶Basic ad
Diagnostics3Basic adjustmentDisplay▶DiagnosticsServiceInfo3.1Pointerp-min.: -5.8 mbarp-max.: 167.5 mbarT-min.: -12.5 °CT-max.: +85.5 °C3.2Sensor statu
6.6 Savingthe parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwar
7 Setupwith PACTware and other adjustmentprograms7.1 Connect the PC via VEGACONNECT312Fig. 26: Connectionof the PC via VEGACONNECT directly to the sen
Necessary components:l VEGABAR 63l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system12 43OPENTWISTUSBLOCKFig
Allcurrently available VEGA DTMs are provided in the DTM Collectionon CD and can be obtained from the responsible VEGA agency for atoken fee. This CD
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
8 Maintenance and fault rectification8.1 MaintainWhen used in the correct way, no special maintenance is required innormal operation.In some applicatio
? 4 … 20 mA signal not stablel Level fluctuationsà Set the integration time via the indicating and adjustmentmodule or PACTwarel no atmospheric pressur
8.3 Exchanging the electronics moduleIn case of a defect, the electronics module can be exchanged by theuser against an identical type. If no electron
l Print and fill out one form per instrumentl Clean the instrument and pack it damage-proofl Attach the completed form and, if need be, also a safety d
9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
10 Supplement10.1 Technical dataGeneral dataPressure type Gauge pressure or gauge pressureMeasuring principle Depending on the measuring range piezore
Output variableOutput signal 4 … 20 mA/HARTHART output values- HART value (Primary Value) Process pressure- HART value (Secondary Value) TemperatureSi
Adjustment range of the zero/span adjustment relating to the nominal measuring range:- zero -5 … +95 %- Span -5 … +105 %Recommended max. turn down 10
Deviation- Turn down 1 : 1 up to 5 : 1 < 0.1 %- Turn down > 5 : 1 < 0.02 % x TDDeviation with absolute pressure measuring range 0.1 bar- Turn
Process conditionsThe speci fications to the pressure stage and the product temperature are used as an overview.The speci fications of the type label ar
2.5 Safetyapproval markings and safety tipsThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device ful
Electromechanical data - version IP 66/IP 67Cable entry/plug19)- Single chamber housing l 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm),1 x blind stop
Connection cable- Configuration four wires, one suspension cable, one breathercapillary, screen braiding, metal foil, mantle- Wire cross-section 0.5 mm
Adjustment elements 4 keysProtection class- unassembled IP 20- mounted into the sensor without cover IP 40Materials- Housing ABS- Inspection window Po
Electrical protective measuresProtection class- Housing, standard IP 66/IP 6721)- Aluminium and stainless housing (op-tionally available)IP 68 (1 bar)
10.2 DimensionsHousing in protection class IP 66/IP 67~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")ø 77
Housing in protection IP 66 /IP 68 (1 bar)117 mm (4.61")120 mm (4.72")~ 103 mm(4.06")~ 105 mm (4.13")ø 77 mm(3.03")116 mm (4.
IP 68 version with external housing1265 mm(2 9/16")68 mm(2 43/64")92 mm(3 5/8")42mm(1 21/32")40mm(1 37/64")90 mm (3 35/64&quo
VEGABAR 63 - threaded fitting23 mm(29/32")G ½ AG ½ B63 mm(2 31/64")65 mm(2 9/16")G1B65 mm(2 9/16")20,5 mm(13/16")10 mm(25/64&q
VEGABAR 63 - hygienic fitting 1LA ø78 mm (3 5/64")82 mm(3 15/64")LAø 90 mm (3 35/64")82 mm(3 15/64")CA ø64 mm (2 33/64")ø84 mm
VEGABAR 63 - hygienic fitting 2KB81 mm(3 3/16")ø 66 mm (2 19/32") ø 83 mm (3 17/64")ø 63 mm (2 31/64")81 mm(3 3/16")81 mm(3 3/
2.10 Environmental instructionsProtection of the environment is one of our most important duties. Thatis why we have introduced an environment managem
VEGABAR 63 - hygienic fitting 3RA81 mm(3 3/16")84 mm(3 3/16")84 mm(3 3/16")ø 74 mm (2 29/32")ø 78 mm (3 5/64") ø 92 mm (3 5/8&
VEGABAR 63 - hygienic fitting 4AA82 mm(3.23")ø 65 mm (2.56")ø 105 mm (4.13")ø 84 mm (3.31")Fig. 38: VEGABAR 63 - AA = DRDVEGABAR 63
VEGABAR 63 - flange connection1 7/64"3 15/32"4 1/64"5 7/16" 1/8" 1/8" 1/8"4xø 45/64"4xø 45/64"8xø 55/64&qu
10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only
74 VEGABAR 63 • 4 … 20 mA/HART10 Supplement32462-EN-081209
VEGABAR 63 • 4 … 20 mA/HART 7510 Supplement32462-EN-081209
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGABAR 63 process pressure transmitterl Documentation- this operating instru
123Fig. 1: Exampleof a VEGABAR 63 with manometer connection G½ A accordingto EN 837 and plastic housing1 Housing cover with integrated indicating and
Commenti su questo manuale